10.2.4 Alarms related to process monitoring are not reported as intended

Note the following when you are monitoring the process operation status of a monitored host that is running UNIX: An error alarm might be reported even though the monitoring target process is not stopped, and then a normal alarm might be reported at the following collection time.

In a UNIX environment, when a process generates child processes, copies of these processes are created, and as a result duplicate copies of the same processes might appear to exist. Therefore, keep in mind that the number of processes increases when a process that generates child processes is the monitoring target. Specifically, an error alarm can be reported if process information is collected at the time the number of processes increases, and a normal alarm can then be reported if process information is collected at the time the number of processes returns to 1.

To avoid this phenomenon, take the following steps:

If the process operation status information could not be collected from the OS, the number of monitoring target processes might become 0 and an alarm might be reported. To prevent this alarm, from the Alarms window, open the New Alarm Table > Main Information window or the Edit > Main Information window. Then in Advanced settings, select Report alarm when the following damping condition is reached and specify 2 occurrence(s) during/Interval(s).