Nonstop Database, HiRDB Version 9 System Operation Guide

[Contents][Index][Back][Next]

26.6.8 Actions to take when a stopped unit prevents switching of the system manager unit

When a system switchover for the system manager unit occurs while there is a stopped unit, it is not possible to start the system manager unit at the switching destination. As a result, the system switchover for the system manager unit fails.

However, if you specify reduced activation, system switchovers for the system manager unit can be performed, even if there is a stopped unit.

The following subsections explain the prerequisites for specifying reduced activation and its limitations on operations.

Organization of this subsection
(1) Using reduced activation

(1) Using reduced activation

When there is a stopped unit, system switchovers for the system manager unit can be performed if the following operands are specified:

The following table lists the values that can be specified for these operands, and it describes the actions HiRDB takes during a system switchover.

Table 26-33 Operands related to reduced activation and actions HiRDB takes during a system switchover

Condition Actions HiRDB takes when a system switchover occurs for the system manager unit
pd_start_level specification value pd_start_skip_unit specification#
0
(default value)
-- If there is a stopped unit, a system switchover for the system manager unit fails.
1 Not specified Even if there is a stopped unit, a system switchover for the system manager unit executes. However, a wait occurs for receipt of a startup processing completion notification from each unit. This notification wait time is specified in the pd_reduced_check_time operand (the default value is 20 minutes).
Specified Even if there is a stopped unit, a system switchover for the system manager unit executes. No notification wait time occurs.

Legend:
--: Need not be specified.

#
When you specify the pd_start_skip_unit operand, you must terminate HiRDB.

Reference note
  • When a system switchover for the system manager unit occurs, a check is made for whether front-end servers and back-end servers are active at the system manager unit at the switching destination. This is why a wait occurs for receipt of a startup processing completion notification from each unit. If a system switchover occurs while there are units that are stopped, the operating status of such units cannot be determined. As a result, the system switchover might fail or take a long time to complete.
  • If any of the following conditions is not satisfied, a system switchover for the system manager unit fails:
    [Figure] A front-end server is active.
    [Figure] A back-end server is active.
    [Figure] A dictionary server is active.